Jiangsu Deli Air Conditioning & Purification Equipment Co., Ltd.
Smoke & Fire Damper (Normally Open Type)
Standard Operation Features:
-
Default Position: Normally open (NO) during regular operation
-
Auto-Shutdown:
-
Fusible link activates at 280°C (BS EN 1366-2 certified)
-
Dual triggering: Thermal sensor + manual override
-
-
Signal Feedback:
-
Provides closed-position signal output (NO/NC contact)
-
-
Reset Mechanism:
-
Manual reset required after activation
-
Safety lock prevents automatic reopening
-
Technical Specifications:
-
Valve Material:
-
Body: 1.5mm galvanized steel (SGCC)
-
Blades: 1.2mm stainless steel (304 grade)
-
-
Operating Conditions:
-
Temperature range: -30°C to +120°C (continuous)
-
Withstands 280°C for 90min (GB 15930-2007)
-
-
Electrical Parameters:
-
Signal contact: SPDT 5A/250VAC
-
Cable: Fire-resistant (IEC 60331 compliant)
-
Certifications:
-
CCCF (China Compulsory Fire Certification)
-
UL 555S Smoke Damper Listing
-
EN 12101-3 Smoke Control Standard
Installation Notes:
-
Must integrate with fire alarm control panel (FACP)
-
Maintain 400mm service clearance for reset operations
-
Duct mounting flanges meet TDCDF 5.1-2018 airtightness class
Ordering Example:
Model: DL-SFD-800NO
Size: 800×800mm
Option:
-
With 24VDC actuator
-
With position indicator
Warning:
“Post-activation inspection required before resetting”
“Do not paint or modify fusible link assembly”






评价